← Vulnerability feed

Vulnerability record · CVE-2014-0750 · published 25 January 2014

CVE-2014-0750: GE Proficy CIMPLICITY WebView gefebt.exe path traversal RCE

Ge · Intelligent Platforms Proficy Hmi\%2fscada Cimplicity

The WebView CimWeb component gefebt.exe in GE Proficy HMI/SCADA CIMPLICITY (through 8.2 SIM 24) and Proficy Process Systems with CIMPLICITY contains a directory traversal flaw (CWE-22). A crafted HTTP request can traverse paths and lead to arbitrary code execution on the HMI/SCADA host.

7.5 CVSS 2.0 High EPSS 70% · top 0.6% CWE-22 · Path traversal
7.5CVSS 2.0 base score
70%EPSS exploitation probability, 30 days
NoNot in CISA KEV
3Affected product versions listed by NVD
6References
17 Jun 2026Last modified by NVD

Description

Directory traversal vulnerability in gefebt.exe in the WebView CimWeb components in GE Intelligent Platforms Proficy HMI/SCADA - CIMPLICITY through 8.2 SIM 24, and Proficy Process Systems with CIMPLICITY, allows remote attackers to execute arbitrary code via a crafted HTTP request, aka ZDI-CAN-1622.

AV:N/AC:L/Au:N/C:P/I:P/A:P

Automated analysis

Generated by VULONE's analysis model from the NVD record, CISA KEV and EPSS data on 19 September 2026. Confidence: medium.

high priorityRemote unauthenticated code execution in a SCADA/HMI product with very high EPSS probability, though no KEV listing or confirmed in-the-wild exploitation is documented.

What it is

The WebView CimWeb component gefebt.exe in GE Proficy HMI/SCADA CIMPLICITY (through 8.2 SIM 24) and Proficy Process Systems with CIMPLICITY contains a directory traversal flaw (CWE-22). A crafted HTTP request can traverse paths and lead to arbitrary code execution on the HMI/SCADA host.

Impact

A remote attacker can execute arbitrary code on the SCADA server, potentially taking control of the HMI/SCADA system.

Attack surface

Reachable over the network via HTTP to the WebView CimWeb service; the CVSS vector AV:N/AC:L/Au:N indicates no authentication or user interaction is required.

Exploitation

Not listed in CISA KEV and no public exploit tags in the references, but EPSS is 0.70223 (99.3rd percentile), indicating high predicted likelihood of exploitation activity.

What to do

  • Apply the GE vendor advisory KB15939 fix or upgrade CIMPLICITY past 8.2 SIM 24.
  • Restrict network access to the WebView CimWeb HTTP service to trusted hosts and segments.
  • Place the SCADA web interface behind a firewall or reverse proxy that normalizes and rejects traversal sequences.
  • Monitor vendor and ICS-CERT advisories for updated patches and workarounds.

Detection

  • Inspect HTTP requests to gefebt.exe for ../ or encoded traversal sequences.
  • Alert on unexpected process creation or file writes originating from the CimWeb/gefebt.exe process.
  • Review web server logs for anomalous requests to CimWeb endpoints from untrusted sources.

This assessment is produced automatically and is not human-reviewed. Verify against the vendor advisory before acting on it.

Affected products

3 vulnerable configurations from NVD's CPE data, grouped by vendor and product.

References

Track CVE-2014-0750 inside VULONE

Watch it alongside the ransomware crews, C2 infrastructure and forum chatter that reference it, query it through the API and pull it into your SIEM over TAXII.

Start free Open in platform

Related vulnerabilities

Same products first, then exploited flaws of the same weakness class.

9.3CVE-2013-2785Intelligent platforms proficy hmi\/scada cimplicity memory buffer overflow vulnerabilityMultiple buffer overflows in CimWebServer.exe in the WebView component in GE Intelligent Platforms Proficy HMI/SCADA - CIMPLICITY before 8.0 SIM 27, …EPSS 3.8%9.3CVE-2013-0654Intelligent platforms proficy hmi\/scada cimplicity improper input validation vulnerabilityCimWebServer in GE Intelligent Platforms Proficy HMI/SCADA - CIMPLICITY 4.01 through 8.0, and Proficy Process Systems with CIMPLICITY, allows remote …EPSS 3.1%7.1CVE-2013-2811Catapultsoftware catapult dnp3 i\/o driver improper input validation vulnerabilityThe (1) Catapult DNP3 I/O driver before 7.2.0.60 and the (2) GE Intelligent Platforms Proficy DNP3 I/O driver before 7.20k, as used in DNPDrv.exe (ak…EPSS 1.8%6.8CVE-2017-12732Intelligent platforms proficy hmi\/scada cimplicity stack-based buffer overflow vulnerabilityA Stack-based Buffer Overflow issue was discovered in GE CIMPLICITY Versions 9.0 and prior. A function reads a packet to indicate the next packet len…EPSS 0.75%6.8CVE-2014-0751Intelligent platforms proficy hmi\%2fscada cimplicity path traversal vulnerabilityThe CIMPLICITY Web-based access component, CimWebServer, does not check the location of shell files being loaded into the system. By modifying the so…EPSS 2.7%6.6CVE-2014-2355Intelligent platforms proficy hmi\/scada cimplicity memory buffer overflow vulnerabilityThe (1) CimView and (2) CimEdit components in GE Proficy HMI/SCADA-CIMPLICITY 8.2 and earlier allow remote attackers to gain privileges via a crafted…EPSS 0.65%4.7CVE-2013-2823Catapultsoftware catapult dnp3 i\/o driver improper input validation vulnerabilityThe (1) Catapult DNP3 I/O driver before 7.2.0.60 and the (2) GE Intelligent Platforms Proficy DNP3 I/O driver before 7.20k, as used in DNPDrv.exe (ak…EPSS 0.76%4.3CVE-2013-0653Intelligent platforms proficy hmi\/scada cimplicity path traversal vulnerabilityDirectory traversal vulnerability in substitute.bcl in the WebView CimWeb subsystem in GE Intelligent Platforms Proficy HMI/SCADA - CIMPLICITY 4.01 t…EPSS 19%

Source: NIST National Vulnerability Database (record CVE-2014-0750), CISA KEV, FIRST EPSS (scores of 2026-09-26). This page is refreshed as NVD updates the record.