Vulnerability record · CVE-2013-2785 · published 31 July 2013
CVE-2013-2785: Intelligent platforms proficy hmi\/scada cimplicity memory buffer overflow vulnerability
Ge · Intelligent Platforms Proficy Hmi\/Scada Cimplicity
Multiple buffer overflows in CimWebServer.exe in the WebView component in GE Intelligent Platforms Proficy HMI/SCADA - CIMPLICITY before 8.0 SIM 27, 8.1 before SIM 25, and 8.2 before SIM 19, and Proficy Process Systems with CIMPLICITY, allow remote attackers to execute arbitrary code via crafted data in packets to TCP port 10212, aka ZDI-CAN-1621 and ZDI-CAN-1624.
Description
Multiple buffer overflows in CimWebServer.exe in the WebView component in GE Intelligent Platforms Proficy HMI/SCADA - CIMPLICITY before 8.0 SIM 27, 8.1 before SIM 25, and 8.2 before SIM 19, and Proficy Process Systems with CIMPLICITY, allow remote attackers to execute arbitrary code via crafted data in packets to TCP port 10212, aka ZDI-CAN-1621 and ZDI-CAN-1624.
AV:N/AC:M/Au:N/C:C/I:C/A:C
Affected products
2 vulnerable configurations from NVD's CPE data, grouped by vendor and product.
References
Track CVE-2013-2785 inside VULONE
Watch it alongside the ransomware crews, C2 infrastructure and forum chatter that reference it, query it through the API and pull it into your SIEM over TAXII.
Related vulnerabilities
Same products first, then exploited flaws of the same weakness class.
Source: NIST National Vulnerability Database (record CVE-2013-2785), CISA KEV, FIRST EPSS (scores of 2026-09-27). This page is refreshed as NVD updates the record.