← Vulnerability feed

Vulnerability record · CVE-2022-38371 · published 11 October 2022

CVE-2022-38371: Siemens nucleus net uncontrolled resource consumption vulnerability

Siemens · Nucleus Net

A vulnerability has been identified in APOGEE MBC (PPC) (BACnet) (All versions), APOGEE MBC (PPC) (P2 Ethernet) (All versions), APOGEE MEC (PPC) (BACnet) (All versions), APOGEE MEC (PPC) (P2 Ethernet) (All versions), APOGEE PXC Compact (BACnet) (All versions < V3.5.7), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.21), APOGEE PXC Modular (BACnet) (All versions < V3.5.7), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.21), Desigo PXC00-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC00-U (All versions >= V2.3 < V6.30.37), Desigo PXC001-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC100-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC12-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC128-U (All versions >= V2.3 < V6.30.37), Desigo PXC200-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC22-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC22.1-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC36.1-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC50-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC64-U (All versions >= V2.3 < V6.30.37), Desigo PXM20-E (All versions >= V2.3 < V6.30.37), Nucleus NET for Nucleus PLUS V1 (All versions < V5.2a), Nucleus NET for Nucleus PLUS V2 (All versions < V5.4), Nucleus ReadyStart V3 V2012 (All versions < V2012.08.1), Nucleus ReadyStart V3 V2017 (All versions < V2017.02.4), Nucleus Source Code (All versions including affected FTP server), TALON TC Compact (BACnet) (All versions < V3.5.7), TALON TC Modular (BACnet) (All versions < V3.5.7). The FTP server does not properly release memory resources that were reserved for incomplete connection attempts by FTP clients. This could allow a remote attacker to generate a denial of service condition on devices that incorporate a vulnerable version of the FTP server.

8.7 CVSS 4.0 High EPSS 1.4% · top 29.2% CWE-400 · Uncontrolled resource consumptionCWE-401 · Memory leak
8.7CVSS 4.0 base score
1.4%EPSS exploitation probability, 30 days
NoNot in CISA KEV
21Affected product versions listed by NVD
8References
17 Jun 2026Last modified by NVD

Description

A vulnerability has been identified in APOGEE MBC (PPC) (BACnet) (All versions), APOGEE MBC (PPC) (P2 Ethernet) (All versions), APOGEE MEC (PPC) (BACnet) (All versions), APOGEE MEC (PPC) (P2 Ethernet) (All versions), APOGEE PXC Compact (BACnet) (All versions < V3.5.7), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.21), APOGEE PXC Modular (BACnet) (All versions < V3.5.7), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.21), Desigo PXC00-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC00-U (All versions >= V2.3 < V6.30.37), Desigo PXC001-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC100-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC12-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC128-U (All versions >= V2.3 < V6.30.37), Desigo PXC200-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC22-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC22.1-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC36.1-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC50-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC64-U (All versions >= V2.3 < V6.30.37), Desigo PXM20-E (All versions >= V2.3 < V6.30.37), Nucleus NET for Nucleus PLUS V1 (All versions < V5.2a), Nucleus NET for Nucleus PLUS V2 (All versions < V5.4), Nucleus ReadyStart V3 V2012 (All versions < V2012.08.1), Nucleus ReadyStart V3 V2017 (All versions < V2017.02.4), Nucleus Source Code (All versions including affected FTP server), TALON TC Compact (BACnet) (All versions < V3.5.7), TALON TC Modular (BACnet) (All versions < V3.5.7). The FTP server does not properly release memory resources that were reserved for incomplete connection attempts by FTP clients. This could allow a remote attacker to generate a denial of service condition on devices that incorporate a vulnerable version of the FTP server.

CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:

Affected products

21 vulnerable configurations from NVD's CPE data, grouped by vendor and product.

References

Track CVE-2022-38371 inside VULONE

Watch it alongside the ransomware crews, C2 infrastructure and forum chatter that reference it, query it through the API and pull it into your SIEM over TAXII.

Start free Open in platform

Related vulnerabilities

Same products first, then exploited flaws of the same weakness class.

9.8CVE-2021-31884Siemens capital vstar vulnerabilityA vulnerability has been identified in APOGEE MBC (PPC) (BACnet) (All versions), APOGEE MBC (PPC) (P2 Ethernet) (All versions), APOGEE MEC (PPC) (BAC…EPSS 1.5%9.8CVE-2021-31886Siemens nucleus net out-of-bounds write vulnerabilityA vulnerability has been identified in APOGEE MBC (PPC) (BACnet) (All versions), APOGEE MBC (PPC) (P2 Ethernet) (All versions), APOGEE MEC (PPC) (BAC…EPSS 3.0%9.1CVE-2021-31345Siemens capital vstar vulnerabilityA vulnerability has been identified in Capital Embedded AR Classic 431-422 (All versions), Capital Embedded AR Classic R20-11 (All versions < V2303),…EPSS 1.6%9.1CVE-2021-31346Siemens capital vstar vulnerabilityA vulnerability has been identified in Capital Embedded AR Classic 431-422 (All versions), Capital Embedded AR Classic R20-11 (All versions < V2303),…EPSS 2.0%9.1CVE-2021-31889Siemens capital vstar vulnerabilityA vulnerability has been identified in Capital Embedded AR Classic 431-422 (All versions), Capital Embedded AR Classic R20-11 (All versions < V2303),…EPSS 2.2%9.1CVE-2021-31890Siemens capital vstar vulnerabilityA vulnerability has been identified in Capital Embedded AR Classic 431-422 (All versions), Capital Embedded AR Classic R20-11 (All versions < V2303),…EPSS 2.2%8.8CVE-2021-31887Siemens nucleus net out-of-bounds write vulnerabilityA vulnerability has been identified in APOGEE MBC (PPC) (BACnet) (All versions), APOGEE MBC (PPC) (P2 Ethernet) (All versions), APOGEE MEC (PPC) (BAC…EPSS 2.4%8.8CVE-2021-31888Siemens nucleus net out-of-bounds write vulnerabilityA vulnerability has been identified in APOGEE MBC (PPC) (BACnet) (All versions), APOGEE MBC (PPC) (P2 Ethernet) (All versions), APOGEE MEC (PPC) (BAC…EPSS 2.4%

Source: NIST National Vulnerability Database (record CVE-2022-38371), CISA KEV, FIRST EPSS (scores of 2026-09-27). This page is refreshed as NVD updates the record.