Vulnerability record · CVE-2022-33318 · published 20 July 2022
CVE-2022-33318: Mitsubishi Electric GENESIS64 and MC Works64 deserialization RCE
Iconics · Genesis64
GENESIS64, ICONICS Suite, GENESIS32 and MC Works64 contain a deserialization of untrusted data flaw (CWE-502). A remote attacker can send specially crafted packets to the server and execute arbitrary code without authenticating. Because these are HMI/SCADA products, successful exploitation can compromise industrial control environments.
Description
Deserialization of Untrusted Data vulnerability in Mitsubishi Electric GENESIS64 versions 10.97 to 10.97.1, Mitsubishi Electric Iconics Digital Solutions GENESIS64 versions 10.97 to 10.97.1, Mitsubishi Electric ICONICS Suite versions 10.97 to 10.97.1, Mitsubishi Electric Iconics Digital Solutions ICONICS Suite versions 10.97 to 10.97.1, Mitsubishi Electric GENESIS32 versions 9.7 and prior, Mitsubishi Electric Iconics Digital Solutions GENESIS32 versions 9.7 and prior, and Mitsubishi Electric MC Works64 versions 4.04E and prior allows a remote unauthenticated attacker to execute an arbitrary malicious code by sending specially crafted packets to the GENESIS64, ICONICS Suite, GENESIS32, or MC Works64 server.
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Automated analysis
critical priorityCVSS 9.8 with network reachability, no authentication and no user interaction on SCADA/HMI servers makes this a critical pre-auth remote code execution risk.
What it is
GENESIS64, ICONICS Suite, GENESIS32 and MC Works64 contain a deserialization of untrusted data flaw (CWE-502). A remote attacker can send specially crafted packets to the server and execute arbitrary code without authenticating. Because these are HMI/SCADA products, successful exploitation can compromise industrial control environments.
Impact
An unauthenticated remote attacker gains arbitrary code execution on the affected server, typically with the privileges of the service, allowing full control of the host and potential lateral movement into the control network.
Attack surface
The flaw is reachable over the network via crafted packets sent to the GENESIS64, ICONICS Suite, GENESIS32 or MC Works64 server. The CVSS vector shows no privileges required and no user interaction, so it is unauthenticated and remotely triggerable.
Exploitation
Not listed in CISA KEV and no ransomware associations are documented. EPSS is high (0.48137, 98.8th percentile), indicating elevated likelihood of exploitation, but the references are only vendor and advisory links with no public exploit tag.
What to do
- Apply the vendor fixes referenced in the Mitsubishi Electric PSIRT advisory and CISA ICS advisory ICSA-22-202-04.
- If patching cannot be done immediately, isolate affected GENESIS64, ICONICS Suite, GENESIS32 and MC Works64 servers behind strict network segmentation and firewall rules.
- Restrict network access to the affected server ports to trusted engineering and control hosts only; do not expose these systems to untrusted networks.
- Monitor vendor advisories for updated fixed versions and confirm the exact affected build before and after remediation.
- Where feasible, run the affected services under least-privilege accounts to limit the impact of code execution.
Detection
- Monitor network traffic to GENESIS64/ICONICS/MC Works64 servers for anomalous or unexpected packet patterns and connections from non-engineering hosts.
- Alert on unexpected child processes spawned by the affected server services, especially command shells or scripting interpreters.
- Review server and application logs for crashes, deserialization errors or unusual service restarts around suspicious network activity.
- Baseline normal client-server communication and alert on new remote sources contacting the affected services.
This assessment is produced automatically and is not human-reviewed. Verify against the vendor advisory before acting on it.
Affected products
2 vulnerable configurations from NVD's CPE data, grouped by vendor and product.
References
| Link | Tags |
|---|---|
| https://jvn.jp/vu/JVNVU96480474/index.html | Third Party Advisory |
| https://www.cisa.gov/news-events/ics-advisories/icsa-22-202-04 | |
| https://www.mitsubishielectric.com/en/psirt/vulnerability/pdf/2022-008_en.pdf | Third Party Advisory |
| https://jvn.jp/vu/JVNVU96480474/index.html | Third Party Advisory |
| https://www.mitsubishielectric.com/en/psirt/vulnerability/pdf/2022-008_en.pdf | Third Party Advisory |
Track CVE-2022-33318 inside VULONE
Watch it alongside the ransomware crews, C2 infrastructure and forum chatter that reference it, query it through the API and pull it into your SIEM over TAXII.
Related vulnerabilities
Same products first, then exploited flaws of the same weakness class.
Source: NIST National Vulnerability Database (record CVE-2022-33318), CISA KEV, FIRST EPSS (scores of 2026-09-26). This page is refreshed as NVD updates the record.