CVE-2021-25667: Siemens ruggedcom rm1224 firmware stack-based buffer overflow vulnerability
Siemens · Ruggedcom Rm1224 Firmware
A vulnerability has been identified in RUGGEDCOM RM1224 (All versions >= V4.3 and < V6.4), SCALANCE M-800 (All versions >= V4.3 and < V6.4), SCALANCE S615 (All versions >= V4.3 and < V6.4), SCALANCE SC-600 Family (All versions >= V2.0 and < V2.1.3), SCALANCE XB-200 (All versions < V4.1), SCALANCE XC-200 (All versions < V4.1), SCALANCE XF-200BA (All versions < V4.1), SCALANCE XM400 (All versions < V6.2), SCALANCE XP-200 (All versions < V4.1), SCALANCE XR-300WG (All versions < V4.1), SCALANCE XR500 (All versions < V6.2). Affected devices contain a stack-based buffer overflow vulnerability in the handling of STP BPDU frames that could allow a remote attacker to trigger a denial-of-service condition or potentially remote code execution. Successful exploitation requires the passive listening feature of the device to be active.
Description
A vulnerability has been identified in RUGGEDCOM RM1224 (All versions >= V4.3 and < V6.4), SCALANCE M-800 (All versions >= V4.3 and < V6.4), SCALANCE S615 (All versions >= V4.3 and < V6.4), SCALANCE SC-600 Family (All versions >= V2.0 and < V2.1.3), SCALANCE XB-200 (All versions < V4.1), SCALANCE XC-200 (All versions < V4.1), SCALANCE XF-200BA (All versions < V4.1), SCALANCE XM400 (All versions < V6.2), SCALANCE XP-200 (All versions < V4.1), SCALANCE XR-300WG (All versions < V4.1), SCALANCE XR500 (All versions < V6.2). Affected devices contain a stack-based buffer overflow vulnerability in the handling of STP BPDU frames that could allow a remote attacker to trigger a denial-of-service condition or potentially remote code execution. Successful exploitation requires the passive listening feature of the device to be active.
CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Affected products
15 vulnerable configurations from NVD's CPE data, grouped by vendor and product.
References
| Link | Tags |
|---|---|
| https://cert-portal.siemens.com/productcert/pdf/ssa-979775.pdf | PatchVendor Advisory |
| https://us-cert.cisa.gov/ics/advisories/icsa-21-068-03 | PatchThird Party AdvisoryUS Government Resource |
| https://cert-portal.siemens.com/productcert/pdf/ssa-979775.pdf | PatchVendor Advisory |
| https://us-cert.cisa.gov/ics/advisories/icsa-21-068-03 | PatchThird Party AdvisoryUS Government Resource |