← Vulnerability feed

Vulnerability record · CVE-2018-16556 · published 13 December 2018

CVE-2018-16556: Siemens simatic s7-400 firmware improper input validation vulnerability

Siemens · Simatic S7 400 Firmware

A vulnerability has been identified in SIMATIC S7-400 CPU 412-1 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 414F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416-2 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416F-2 DP V7 (All versions), SIMATIC S7-400 CPU 416F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 417-4 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 PN V7 (All versions < V7.0.3), SIMATIC S7-400 H V4.5 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants) (All versions < V6.0.9), SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-410 CPU family (incl. SIPLUS variants) (All versions < V8.2.1), SIPLUS S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 V7 (All versions), SIPLUS S7-400 CPU 417-4 V7 (All versions). Specially crafted packets sent to port 102/tcp via Ethernet interface, via PROFIBUS, or via Multi Point Interfaces (MPI) could cause the affected devices to go into defect mode. Manual reboot is required to resume normal operation. Successful exploitation requires an attacker to be able to send specially crafted packets to port 102/tcp via Ethernet interface, via PROFIBUS or Multi Point Interfaces (MPI). No user interaction and no user privileges are required to exploit the security vulnerability. The vulnerability could allow causing a denial of service condition of the core functionality of the CPU, compromising the availability of the system.

7.5 CVSS 3.1 High EPSS 1.5% · top 26.0% CWE-20 · Improper input validation
7.5CVSS 3.1 base score, v2 7.8
1.5%EPSS exploitation probability, 30 days
NoNot in CISA KEV
5Affected product versions listed by NVD
2References
17 Jun 2026Last modified by NVD

Description

A vulnerability has been identified in SIMATIC S7-400 CPU 412-1 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 414F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416-2 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416F-2 DP V7 (All versions), SIMATIC S7-400 CPU 416F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 417-4 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 PN V7 (All versions < V7.0.3), SIMATIC S7-400 H V4.5 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants) (All versions < V6.0.9), SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-410 CPU family (incl. SIPLUS variants) (All versions < V8.2.1), SIPLUS S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 V7 (All versions), SIPLUS S7-400 CPU 417-4 V7 (All versions). Specially crafted packets sent to port 102/tcp via Ethernet interface, via PROFIBUS, or via Multi Point Interfaces (MPI) could cause the affected devices to go into defect mode. Manual reboot is required to resume normal operation. Successful exploitation requires an attacker to be able to send specially crafted packets to port 102/tcp via Ethernet interface, via PROFIBUS or Multi Point Interfaces (MPI). No user interaction and no user privileges are required to exploit the security vulnerability. The vulnerability could allow causing a denial of service condition of the core functionality of the CPU, compromising the availability of the system.

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

Affected products

5 vulnerable configurations from NVD's CPE data, grouped by vendor and product.

References

Track CVE-2018-16556 inside VULONE

Watch it alongside the ransomware crews, C2 infrastructure and forum chatter that reference it, query it through the API and pull it into your SIEM over TAXII.

Start free Open in platform

Related vulnerabilities

Same products first, then exploited flaws of the same weakness class.

8.7CVE-2017-12741Siemens simatic s7-200 firmware uncontrolled resource consumption vulnerabilitySpecially crafted packets sent to port 161/udp could cause a denial of service condition. The affected devices must be restarted manually.EPSS 3.3%8.2CVE-2018-16557Siemens simatic s7-400 firmware improper verification of cryptographic signature vulnerabilityA vulnerability has been identified in SIMATIC S7-400 CPU 412-1 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 DP V7 (All versions), SIMATIC S7-400 C…EPSS 0.82%7.5CVE-2022-25622Siemens simatic cfu diq firmware uncontrolled resource consumption vulnerabilityThe PROFINET (PNIO) stack, when integrated with the Interniche IP stack, improperly handles internal resources for TCP segments where the minimum TCP…EPSS 0.88%7.5CVE-2021-40368Siemens simatic s7-400h v6 firmware memory buffer overflow vulnerabilityA vulnerability has been identified in SIMATIC S7-400 CPU 412-1 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 DP V7 (All versions), SIMATIC S7-400 C…EPSS 1.0%7.5CVE-2019-10936Siemens dk standard ethernet controller firmware uncontrolled resource consumption vulnerabilityAffected devices improperly handle large amounts of specially crafted UDP packets. This could allow an unauthenticated remote attacker to trigger a d…EPSS 2.1%7.5CVE-2018-4850Siemens simatic s7-400 firmware improper input validation vulnerabilityA vulnerability has been identified in SIMATIC S7-400 (incl. F) CPU hardware version 4.0 and below (All versions), SIMATIC S7-400 (incl. F) CPU hardw…EPSS 2.4%7.1CVE-2017-2681Siemens simatic cp 343-1 std firmware uncontrolled resource consumption vulnerabilitySpecially crafted PROFINET DCP packets sent on a local Ethernet segment (Layer 2) to an affected product could cause a denial of service condition of…EPSS 0.91%7.1CVE-2017-2680Siemens simatic cp 343-1 std firmware uncontrolled resource consumption vulnerabilitySpecially crafted PROFINET DCP broadcast packets could cause a denial of service condition of affected products on a local Ethernet segment (Layer 2)…EPSS 1.1%

Source: NIST National Vulnerability Database (record CVE-2018-16556), CISA KEV, FIRST EPSS (scores of 2026-09-29). This page is refreshed as NVD updates the record.