← Vulnerability feed

Vulnerability record · CVE-2011-3486 · published 16 September 2011

CVE-2011-3486: Beckhoff TwinCAT UDP request out-of-bounds read causes denial of service

Beckhoff · Twincat

Beckhoff TwinCAT 2.11.0.2004 and earlier performs an out-of-bounds read when handling a crafted request sent to UDP port 48899, which can crash or otherwise deny service. The flaw is remotely reachable without authentication, so any host that can send UDP packets to the port can trigger it.

5.0 CVSS 2.0 Medium EPSS 50% · top 1.1% CWE-119 · Memory buffer overflow
5.0CVSS 2.0 base score
50%EPSS exploitation probability, 30 days
NoNot in CISA KEV
1Affected product versions listed by NVD
10References, 2 tagged exploit
16 Jun 2026Last modified by NVD

Description

Beckhoff TwinCAT 2.11.0.2004 and earlier allows remote attackers to cause a denial of service via a crafted request to UDP port 48899, which triggers an out-of-bounds read.

AV:N/AC:L/Au:N/C:N/I:N/A:P

Automated analysis

Generated by VULONE's analysis model from the NVD record, CISA KEV and EPSS data on 20 September 2026. Confidence: medium.

high priorityUnauthenticated remote denial of service on an industrial control product with a public exploit reference and very high EPSS, though no KEV listing or code execution.

What it is

Beckhoff TwinCAT 2.11.0.2004 and earlier performs an out-of-bounds read when handling a crafted request sent to UDP port 48899, which can crash or otherwise deny service. The flaw is remotely reachable without authentication, so any host that can send UDP packets to the port can trigger it.

Impact

An unauthenticated remote attacker can cause a denial of service on the affected TwinCAT system, disrupting control or engineering operations. The record describes only an out-of-bounds read, so no code execution or data disclosure is claimed.

Attack surface

Reached over the network via a crafted UDP packet to port 48899; the CVSS vector AV:N/AC:L/Au:N indicates no authentication and no user interaction are required.

Exploitation

Not listed in CISA KEV and no ransomware use is documented, but EPSS is high (0.4965, 98.8th percentile) and a public exploit reference is tagged, so exploitation is plausible and likely.

What to do

  • Upgrade TwinCAT to a version later than 2.11.0.2004, or apply the vendor fix referenced in the US-CERT ICS alert.
  • Restrict network access to UDP port 48899 to trusted engineering hosts using firewall or ACL rules.
  • Segment TwinCAT systems from general IT and untrusted networks to limit who can reach the port.
  • Monitor and log traffic to UDP port 48899 for unexpected or malformed packets.

Detection

  • Alert on unexpected or malformed UDP traffic to port 48899 from hosts outside the engineering network.
  • Monitor TwinCAT service crashes, restarts or loss of availability and correlate with inbound UDP 48899 packets.
  • Baseline which hosts legitimately communicate on UDP 48899 and flag new or anomalous sources.

This assessment is produced automatically and is not human-reviewed. Verify against the vendor advisory before acting on it.

Affected products

1 vulnerable configurations from NVD's CPE data, grouped by vendor and product.

References

Track CVE-2011-3486 inside VULONE

Watch it alongside the ransomware crews, C2 infrastructure and forum chatter that reference it, query it through the API and pull it into your SIEM over TAXII.

Start free Open in platform

Related vulnerabilities

Same products first, then exploited flaws of the same weakness class.

9.8CVE-2019-16871Beckhoff twincat authentication bypass by spoofing vulnerabilityBeckhoff Embedded Windows PLCs through 3.1.4024.0, and Beckhoff Twincat on Windows Engineering stations, allow an attacker to achieve Remote Code Exe…EPSS 5.3%9.1CVE-2017-16726Beckhoff twincat improper authorization vulnerabilityBeckhoff TwinCAT supports communication over ADS. ADS is a protocol for industrial automation in protected environments. ADS has not been designed to…EPSS 0.51%9.1CVE-2014-5415Beckhoff embedded pc images permissions and access controls vulnerabilityBeckhoff Embedded PC images before 2014-10-22 and Automation Device Specification (ADS) TwinCAT components might allow remote attackers to obtain acc…EPSS 4.3%9.1CVE-2014-5414Beckhoff embedded pc images improper restriction of authentication attempts vulnerabilityBeckhoff Embedded PC images before 2014-10-22 and Automation Device Specification (ADS) TwinCAT components do not restrict the number of authenticati…EPSS 4.8%7.8CVE-2018-7502Beckhoff twincat improper input validation vulnerabilityKernel drivers in Beckhoff TwinCAT 3.1 Build 4022.4, TwinCAT 2.11 R3 2259, and TwinCAT 3.1 lack proper validation of user-supplied pointer values. An…EPSS 0.56%7.5CVE-2019-5636Beckhoff twincat improper resource shutdown vulnerabilityWhen a Beckhoff TwinCAT Runtime receives a malformed UDP packet, the ADS Discovery Service shuts down. Note that the TwinCAT devices are still perfor…EPSS 1.4%7.5CVE-2019-5637Beckhoff twincat divide by zero vulnerabilityWhen Beckhoff TwinCAT is configured to use the Profinet driver, a denial of service of the controller could be reached by sending a malformed UDP pac…EPSS 1.4%5.9CVE-2017-16718Beckhoff twincat insufficiently protected credentials vulnerabilityBeckhoff TwinCAT 3 supports communication over ADS. ADS is a protocol for industrial automation in protected environments. This protocol uses user co…EPSS 0.42%

Source: NIST National Vulnerability Database (record CVE-2011-3486), CISA KEV, FIRST EPSS (scores of 2026-09-26). This page is refreshed as NVD updates the record.